Cleaning of submersible pressure transmitters or level probes

If the precise pressure sensor design of the submersible pressure transmitter or level probe is selected to measure the filling levels, this often means that the probe can be used under environmental requirements which may cause failure of common level sensors.
The most unfortunate circumstances such as soiled media, abrasive ingredients and sludge when found in wastewater treatment plants, brackish and wastewater tanks or even digester towers, impose special requirements on the design of a submersible pressure transmitter. Focus of many requirements on a submersible pressure transmitter would be to have the lowest possible susceptibility to contamination or build-up of the pressure sensor by optimizing its design. This is why the normal design of a pressure transmitter with narrow pressure ports is not used within level probes because it would tend to clog in such applications.
The design of the submersible pressure transmitter and its own pressurised sensor diaphragm is optimised to experience very low susceptibility to contamination. However, continuous operation in soiled media may lead to sticking of dirt particles on the stainless steel diaphragm. To get the highest accuracy and fastest response times in the event of level change, the thickness of this stainless steel diaphragm is already minimised ex factory to just a few microns. Therefore, cleaning of the diaphragm must be carried out with caution. Always stay away from Funniest or edged tools. It is also strongly advised not to use the commonly used screwdrivers or pens.
If cleaning of the sensor diaphragm is necessary, then rinse it using a weak water jet or clean it carefully using compressed air. Damage of the diaphragm because of denting or notching, even though it seems to be purely superficial, leads to significant losses in the accuracy of level measurement. Deformation of the diaphragm often shifts the zero point of the pressure measurement in the internal electronic measurement system and also distorts the output signal linearisation which has been adjusted ex works to the undamaged diaphragm. Thus, the submersible pressure transmitter with damaged diaphragm generates falsified measurement of the existing filling level and, therefore, cannot be considered a trusted measuring instrument any more. Thus, complete replacement of the damaged instrument is completely necessary.
Please find further information on this topic on our information platform ?Hydrostatic level measurement?